SKU: svv 005/R/C
Manufacturer: Pavliš a Hartmann
Fire hydrant systems with form-fitting hose are a very effective extinguishing agent with a constant water supply that is instantly accessible.
According to ČSN 73 0873 and ČSN EN 671-1
Fire hydrant systems with a shape-resistant hose are a very effective extinguishing agent with a constant water supply that is immediately accessible. The requirements for these systems are such as to ensure prompt operation by one person.
Colour red RAL 3000.
Width | Height | Depth |
---|---|---|
650 | 650 | 210 |
Inspection of hydrant systems is carried out by a trained inspection technician in accordance with the relevant standards and regulations.
When selecting a specific type of equipment, hose systems with a hose with a nominal clearance of at least 25 mm are mainly fitted with:
a) in fire compartments of production halls (according to ČSN 73 0804) and warehouses (according to ČSN 73 0845)
(b) in fire compartments (buildings) with linear fire spread rate v1 > 1.2 m/min; without further proof, values of v1 according to Table B.1 in Annex B may be used for selected premises
(c) in buildings or parts of buildings designed as
- indoor assembly areas (according to CSN 73 0831)
- buildings for accommodation of group OB 4 (according to CSN 73 0833)
- retail outlets and sales warehouses
- collective garages
- exhibition grounds
- film, television and radio studios
- stages and backstage, prop and scenery stores
- fire compartments in underground floors where the number of persons according to EN 73 0818 exceeds 10
- fire compartments with high fire loads (p > 120 kg/m2 )
In other required cases it is sufficient to install hose systems with a nominal hose clearance of at least 19 mm.
The hose systems shall be installed at a height of 1,1 to 1,3 metres above the floor (measured to the centre of the installation). They shall be positioned so that they can be easily accessed by persons and the doors can be opened 180°. A water supply must be provided for the installation to allow a minimum of 0,2 MPa overpressure at the least favourable point.
After opening the cabinet, check that the jet line is closed, open the ball valve on the inlet (the system will water). From the reel, unwind the required amount of hose to the fire point and turn the jet head to set the desired water flow pattern.
Need a wholesale quote? Contact us here.
Choose from similar products
Czech manufacturer
Express delivery times
Warranty, post-warranty service
Professional consulting
Pavliš a Hartmann, spol. s r.o.
V Telčicích 249 (map)
533 12 Chvaletice
Czech Republic
Useful links
Your browser (Internet Explorer) is out of date.
It no longer releases updates for Windows. Download one of these up-to-date, free and excellent browsers: